Product Name | Fluke T+Pro Canada Electrical Tester Safer than traditional solenoid testers and fully compliant with NFPA 70E |
Item NO. | 548623 |
Measuring testers | Electrical tester |
Weight | 1.2 kg = 2.6455 lb = 42.3288 oz |
Category | Phone repair tools |
Tag | T+PRO , Fluke T+Pro , Electrical Tester , Fluke electrical tester , Fluke electric tester , Fluke electronic tester , electronic tester |
Brand | FLUKE |
Creation Time | 2019-09-11 |
Safer than traditional solenoid testers and fully compliant with NFPA 70E*
The T+PRO Electrical Testers offer all the functionality that electricians look for in volt meters and voltage and continuity testers:
Safer than traditional solenoid testers:
Specifications | ||
Temperature | Operating | -10°C to 55°C (14°F to 131°F) |
Storage | -30°C to 60°C (-22°F to 140°F) | |
Relative humidity | 90% | 0°C to 30°C (32°F to 86°F) |
75% | 30°C to 40°C (86°F to 104°F) | |
45% | 40°C to 50°C (104°F to 122°F) | |
Altitude | Operating | 2,000 m (approx. 6,561.6 ft) |
Storage | 10,000 m (approx. 32,808.4 ft) | |
Battery type/life | AAA (2); 40 hours | |
Shock, vibration | Sinusoidal vibration per MIL-PRF-28800F for a Class 2 instrument | |
Safety |
ISA-82.02.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C22.2 No. 61010-1 Second Edition, IEC 61010 - 1 to 1000 V CAT III/600 V CAT IV Compliance to NFPA 70E1 |
|
AC bandwidth | 45 Hz to 66 Hz | |
Maximum working Voltage | 1000 V AC/DC | |
Maximum measurable voltage | 600 V AC/DC | |
Duty cycle | Indefinitely for voltages up to 240 V | |
For voltages between 240 V and 600 V the duty cycle is 30 s on / 300 s off | ||
For voltages above 240 V the tester must connect to a voltage source only for a MAXIMUM of 30 s and then disconnect for a MINIMUM of 300 s | ||
Voltage hazard LED | LEDs turn on at voltages > 30 V AC/DC ±35% | |
LED voltage indication levels | 12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 347 V, 480 V, 600 V | |
LEDs | LEDs turn on between 90% and 100% of the indicated voltage on the LED, except for the 12 V LED which turns on between 50% and 100% | |
LCD accuracy | AC voltage | ±(3% rdg + 2 digits) |
DC voltage | ±(2% rdg + 2 digits) | |
Resistance | ±(5% rdg + 3 digits) | |
LCD resolution | 0.1 V for voltages < 50 V, 1 V for voltages ≥ 50 V | |
0.01 kΩ for resistance measurement | ||
GFCI test current | 100 V - 150 V @ 6 mA - 9 mA AC, 150 V - 240 V < 12 mA | |
Standard input test current | < 5 mA | |
Size (H x W x L) | 1.3 x 2.15 x 7.6 in (3.3 x 5.46 x 19.3 cm ) | |
Weight | 9.9 oz (0.28 kg) | |
1. When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment. |